Bell Options
The Bell Options window allows you to specify what type of alarm output the panel initiates for different types of alarms.
Go to Program > Bell Options.
Available actions include: Steady, Pulse, and Temporal 3, Temporal 4, and None. Selecting None for an alarm event will cause no alarm to sound for the specified type of alarm. Select actions as needed in each of the following options:
Fire Bell Action
Burglary Bell Action
Supervisory Bell Action
Panic Bell Action
Emergency Bell Action
Aux 1 Bell Action
Aux 2 Bell Action
Carbon Monoxide Action
In Bell Cutoff Time, enter the maximum number of minutes for the bell output to remain on. Range is 1-99 minutes. Default is 15 minutes.
To enable an automatic 2 second bell test each time an area is completely armed from a keypad, select Automatic Bell Test.
In Bell Output, enter the output number to follow the panel bell output operation for all actions and off conditions. To disable the output, enter 0. Default is 0.
Note: Bell Output should not be programmed for a Model 1135/1135DB Wireless Siren when programmed in Output Information with Trip with Panel Bell enabled.